Pertronic F120A and F100A Loop Length Calculator
ItemsNo of units Quiescent
Current
Total
Quiescent
Current
Apartment Module 7 mA0 mA
Loop Relay 6 mA0 mA
Loop Responder (Loop Powered) 27 mA0 mA
Loop Responder (Ext Powered) 7 mA0 mA
Conventional Smoke Detectors ++ 0.05 mA0 mA
Analogue Modules 0.35 mA0 mA
Analogue Detectors 0.35 mA0 mA
PS2 Sounder 24V 0.004 mA0 mA
Fan Controller, Fan Relay 15 mA0 mA
PSB Sounder 1.5 mA0 mA
6500S Analogue Beam 2 mA0 mA
Maximum Loop Current: Single End MUST NOT Exceed350 mA
Total Loop Current = TQmaxLoad OK0 mA
Panel Battery Voltage26 Volts
Peak Loop Voltage24 Volts
Minimum Working Loop Voltage15 Volts
Maximum Loop Volt Drop = VD9 Volts
Cable Resistance Ohms/M (F100ZZCBL:1.25mm2 Twisted Pair Cable)0.0312 Ohms
Maximum Allowable Loop Cable Resistance = VD/TQmax (Ohms)**0 Ohms
Maximum Cable Loop Length Must Not Exceed2500 Meters
Maximum Loop Length (m) - Load Spread Evenly Over Loop0 Meters
Maximum Loop Length (m) - Load at end of Loop0 Meters

** To measure Analogue Loop Cable Resistance:
a) short the cable pair at one end.
b) measure the resistance across the two conductors - red to black.

++ Include only Conventional Smoke Detectors connected to Loop      Powered Loop Responders and Apartment Modules.
     
Max Cable Length =
Max Cable Length =
0 M
0 M
0
0